ZJ-DLQ03
Circuit breaker trip comprehensive test machine
Keywords:
Product Description
1. Overview:
This equipment is designed and manufactured in accordance with GB10963.1-2005 Article 9.10, GB14048.1-2006 Article 7.2.1, and JB/T8979-2006 Article 8.13 national standards. It can perform delayed tripping characteristic tests on circuit breakers, i.e., apply 1.13 times, 1.45 times, and 2.55 times the rated current for testing to see if it trips within the specified time; it can also perform instantaneous tripping characteristic tests on circuit breakers, i.e., apply 3~14 times the rated current for testing to see if it trips within the specified time; it is suitable for online factory testing of MCCB circuit breakers and is an essential equipment for electrical performance testing by circuit breaker manufacturers. This equipment has the functions of fast product loading, automatic testing, and automatic judgment.
The equipment cabinet is assembled with high-quality aluminum alloy steel, and the sheet metal is sprayed and sealed. The surface is sprayed with anti-static, anti-rust, and anti-corrosion coatings. The upper part of the equipment is equipped with a stainless steel etched panel, power switch. The equipment is reasonably designed, easy to use, simple to operate, reliable in performance, and beautiful in appearance.
2. Working Principle:
This test bench adopts the principle of low voltage and high current output, using the internal high current isolation transformer to output current. The current size is set by the computer to control the PLC, and the constant current source adjusts the primary input voltage of the transformer to adjust the output current, which has the function of automatically stabilizing the current. The touch screen display sets the test time and compares it with the test tripping time to determine the quality of the circuit breaker. It can test 100A~650A circuit breakers.
Main Technical Parameters
1. Equipment input power: three-phase 380V/50HZ/50KVA;
2. Equipment control mode: PLC+ computer control
3. Protection function: short circuit protection, overload protection, leakage protection;
4. Operating environment temperature: 0 ~ +40℃;
5. Relative humidity: (20 ~ 90)%RH;
6. Equipment dimensions: 1700*900*1800mm high
7. Tested products: 63A~650A MCCB products
8. Current output waveform: sine wave (the distortion of the corrected equipment current waveform is not more than 5%, and the system error is not more than 3%)
9. Current control mode: automatic adjustment;
10. Instantaneous tripping test parameters:
1) Output voltage: 0~16V
2) Voltage accuracy: Level 3;
3) Output current: AC 600A~10000A; 2000~5000A can be energized for 5S, 5000~10000A can be energized for 1S,
4) Resolution: 1A
5) Current accuracy: Level 3;
6) Timing time: 1~9999ms;
7) Action time upper limit setting: 1~5000ms;
8) Action time lower limit setting: 1~5000ms;
9) Transformer ratio: 500/5A, 2000/5A, 10000/5A;
10) Test result: automatic judgment
11. Delayed tripping test parameters:
1) Output voltage: 0~4V
2) Output current: AC 70A~2040A; long-term power on
3) Resolution: 0.1A
4) Current accuracy: Level 1;
5) Timing time: 1~999999s;
6) Action time upper limit setting: 1~999999s;
7) Action time lower limit setting: 1~999999s;
8) Transformer ratio: 200/5A, 2000/5A;
9) The current automatically rises to 1.45 times for testing after the 1.13 times test is completed;
10) Test result: automatic judgment
4. Temperature Rise and Power Consumption Test:
1) Output current: 250~2000A
2) 8 temperature measurement channels, temperature resolution 0.1 degrees
3) Accuracy: Level 0.5, measurement and control speed is 0.1 seconds per channel.
4) Wiring for temperature rise test: 16, 25, 50, 70, 95, 120, 150 square meters, each specification is 2 meters long, quantity 2;
5) Special glue for temperature rise: 1 bottle
6) Degumming water: 1 bottle
7) Measurement range 0~200 degrees;
8) Thermocouple model: T type
5. Heating Box:
1) Equipment built-in heating box: temperature control range: normal temperature +10 degrees ~ 50 degrees
2) Temperature resolution: 0.1 degrees, accuracy 1%±1 degree
3) Temperature stability: ±3 degrees